Neoline series, PWM (Pulse Width Modulation) and IGBT technology, microprocessor controlled, full sinus output Uninterruptible Power Supplies Series.

Features:

Microprocessor controlled

Double-conversion Online

Input power factor raised> 0.98

Highly efficient operation

Sine wave THD <3%

Static bypass system

Overload and short circuit protected

Run time from optional battery

Easy-to-understand front panel displays

RS232 remote monitoring software and dry contact alarm outputs

TUV conforms to international standards such as ISO9001, CE

 

 

Output power factor up to 0.8 is suitable for future load changes and provides higher load capacity
Active Power Factor Correction (PFC) technology enables the input power factor to approach 1 and significantly reduce the mains disturbance noisies.
Wide input voltage range is suitable for all demanding conditions.
The perfect input frequency range ensures that the UPS is suitable for different power sources such as a generator.

High Reliability
Modern DSP digital control technology provides high quality, performance and reliability.
High overload capacity, better compatibility with load and convenience for loads in various types
It provides strong immunity against electromagnetic interference according to EMC requirements of IEC 61000-4 standard.

Scope of application
Local networks (Lan)
Cash register
Telekom
Medical devices
Industrial control
Defense industry
Petrochemical
Ports and other important economic information fields
 
Key Features
Modern DSP digital control technology dramatically increases the performance and system reliability of the products.

Output power factor up to 0.8 is suitable for future load changes and provides higher load capacity.

High overload capacity, better compatibility with the load, and suitability for loads on a variety of loads, reduces total power factor power losses and utilization costs to as low as 90%.

High scalability: Fully satisfies customer requirements.

Emergency power off (EPO): The UPS can be turned off instantaneously in any emergency.

Power (kVA) 2 3 5 6 10 15

 INPUT

Voltage 230 Vac,+/-15%
By-pass Voltage 230 Vac, +/- 10%
Current 13A 19A 30A 35A 44A 58A 87A
Input Frequency 50 Hz(60Hz), +/- %5
EMI EN50091-2 Class A.
Input Voltage Protection Electronic input tolerance external protection

OUTPUT

Power (kW) 1,4 2,1 3,5 4,2 5,25 7 10,5
power factor 0,7
Voltage 230 Vac, +/- 1%
Frequency 50 Hz (60 Hz)
Frequency tolarance +/-2% (synchronize to network)
+/- 0,2% (self-operating)
efficiency %100 load 85-87% 86-90%
Crest faktor 3:1
OverLoad Protection 100%125% load :10 minute
125%150% load :1 minute
<150% load : by pass
Short-Circuit Protection Electronic short-circuit Protection
Output Voltage Protection Electronic Output Voltage tolerance out protection
THD (Total harmonic distortion) <3%
Communication Dry contact & RS232

 BATTERIES

Type Full closed dry type maintenance is not required
Battery quantity 14 14 16 20
Charging voltage 189 VDC 189 VDC 216 VDC 270 VDC
Discharge end voltage 140 VDC 140 VDC 160 VDC 200 VDC
Battery cabinet Internal external
Battery operating temperature 25 C
Battery Protection Automatic circuit breaker
Battery Voltage Protection Electronic battery voltage out of tolerance protection
Battery test Optionally

 

3 Phase Input / 1 Phase Output On Line UPS......

 

3 Phase Input / 3 Phase Ouput On Line UPS ......